UPS ICA SE Series Model; SE 6100 6000VA 192V (Stream Line Type)
Description :
UPS SE6100
Capacity : 6000 VA / 5400 W
AC Voltage : 120 ~ 276 V
AC Frequency : 45 ~ 65 Hz
AC Protection : 40 A
DC Voltage : 192 V
DC INT Battery : 16 x 12 V, 7 Ah
DC Protection : FUSE
CHG Topology : SWITCHING REGULATION
CHG Floating Voltage : 217.6 V
INV Wave Form : SINEWAVE
INV Distorsion : < 3% THD
INV Topology : Online Double Conversion
INV Voltage : 220 1% V
INV Frequency : 50 1% Hz
INV Efficiency : > 90%
Transfer Time When AC In Loss : 0 ms
Transfer Time STS : 0 ms Inverter to Bypass, 0 ms Back To Inverter
Back Up Time : 10 min
BZR AC Input Abnormall : INTERMITTENT SOUND WITH 2 SECONDS INTERVAL
BZR Battery Low : INTERMITTENT SOUND WITH 1 SECONDS INTERVAL
Opera Temp : 0 40 C
Dimension(DxWxH) : 502 x 250 x 616 mm
Weight : 67 Kg
JIKA ADA PERTANYAAN LEBIH LANJUT, SILAHKAN HUBUNGI KAMI DI:
021-2263-2285 / 0812-8227-1418
NOMOR TELEPON DAN WHATSAPP AKTIF